Anonymous
Mar 07, 2026
Rating: 5/5
Reliable Performance
No drift over six months of continuous operation. Power consumption is low which is good for our backup systems.
Description
Reviews
| Brand | - |
| Category | Electronic Components / Maker DIY / Computer Hardware, Monitors & Peripherals |
| Origin | - |
| Communication Protocol | Modbus RTU |
| Interface Type | RS485 Two-Wire |
| Mounting Style | DIN-Rail 35mm |
| Temperature Range | -40°C to 80°C |
| Humidity Range | 0% to 100% RH Non-condensing |
| Temperature Accuracy | ±0.5°C at 25°C |
| Humidity Accuracy | ±3% RH at 25°C |
| Power Supply Voltage | 12V DC to 24V DC |
| Housing Material | Flame Retardant PC |
| Dimensions | 90mm x 18mm x 65mm |
Anonymous
Mar 07, 2026
Rating: 5/5
Reliable Performance
No drift over six months of continuous operation. Power consumption is low which is good for our backup systems.
Anonymous
Mar 06, 2026
Rating: 4/5
Solid Unit
Works well in our server enclosure. Wiring diagram could be clearer but once connected it functions perfectly.
Anonymous
Feb 25, 2026
Rating: 5/5
High Precision
Noticed immediate improvement in monitoring compared to our old sensors. Setup was straightforward using Modbus Poll.
Anonymous
Feb 02, 2026
Rating: 5/5
Perfect for Data Center
Integrated smoothly with our building management system. The readings are consistent and the DIN rail mount is very secure.
Anonymous
Jan 29, 2026
Rating: 5/5
Easy Installation
DIN rail clip snapped in easily. Great value for the precision offered. Highly recommend for industrial cabinets.
Q: Is this compatible with standard Modbus software?
A: Yes, it works with any standard Modbus RTU master software or PLC.
Q: How many devices can be on the same bus?
A: You can connect up to 32 nodes on a single RS485 bus without a repeater.
Q: Can this be used outdoors?
A: This unit is designed for indoor use in enclosures. For outdoor use, please ensure a weatherproof housing.
Q: What is the power consumption?
A: The module consumes less than 1W during normal operation.
Q: What type of cable is recommended for connection?
A: Shielded twisted pair cable is recommended to minimize interference over long distances.